Pulse is Okay, but Doublet is Better

Picking the best Bump Test is Essential when Tuning PID Controllers

In order to tune a PID controller, a change to the process must be observed. The bump test is how practitioners initiate such a change and reveal the cause-and-effect relationship that exists between a loop’s Process Variable (PV) and its Controller Output (CO). In the absence of a bump test, tuning a plant’s PID controllers is little more than guesswork.

There are various types of bump tests that can be performed. The Step, Pulse, Doublet and PBRS are among the most commonly used. Some are more practical than others. Here we focus on the Pulse and Doublet tests since both allow practitioners to observe the process moving in opposite directions.

Pulse Test

The Pulse test involves the execution of two steps both in succession and in opposite directions. It begins by moving a controller’s Set Point (SP) in one direction. Best-practice is to move SP by a value that is 3-4 times the noise evident in the process. When the measured Process Variable (PV) shows a response to the change the SP is then stepped in the opposite direction and returned to its original value. While the Pulse test shows the process moving in both directions, it only reveals one-half of a process’ dynamic behavior. As such it is not the best test. The Doublet is the superior option.

Doublet Test

The Doublet test is essentially two Pulse tests that are conducted in rapid succession and that span both sides of a controller’s normal range of operation. Like the Pulse test the Doublet begins by moving the controller’s SP in one direction so that a clear response to the PV results. A key difference comes into play once the process initially responds to the change. Instead of returning the SP to its original value the SP is moved in the opposite direction and to the other side of the process’ operating range. Note that it’s not necessary for the process to settle at either of these two new SP values. The test is completed by returning the controller’s SP to its original value.

Why is the Doublet Test the best?

Whenever practical Control Station highly recommends the Doublet Test when tuning PID control loops. The Doublet provides data that is representative of a controller’s full range of operation. In contrast with a Pulse that only examines one side of a controller’s operating range, the model and tuning parameters resulting from a Doublet test allow for safer and more effective control.

These resources offer related content:

students and jack

What should you expect from Process Control training?

How Process Control and PID Tuning training expands your manufacturing skill set Searching for meaningful Industrial Professional Development courses can be frustrating. It’s generally understood that Process Control is an important aspect of a practitioner’s job responsibilities. Even so, it’s often unclear what specific knowledge...
Shot,Of,Corridor,In,Working,Data,Center,Full,Of,Rack

3 Truths of Process Analytics and Optimization

The pursuit of optimized production is not as farfetched as it used to be. Today’s manufacturers have access to more useful data, and they possess advanced tools that supply more information than ever before. In spite of the possibilities and the technological advances, however, many...
shutterstock_207048508

How Can I Correct for Noise Using Internal Filters?

  Internal Filters are an Effective Solution for Addressing Noise.  Just Don't be Fooled ...They Don't Solve Everything! Noise is inevitable. To one degree or another it’s evident in the data of most every production process. Sure it can be absent in academic settings and...

Still looking for more?

Now that you’ve gotten the basics, connect with our team to learn how our people, processes and technologies can help you optimize.