Pulse is Okay, but Doublet is Better

Picking the best Bump Test is Essential when Tuning PID Controllers

In order to tune a PID controller, a change to the process must be observed. The bump test is how practitioners initiate such a change and reveal the cause-and-effect relationship that exists between a loop’s Process Variable (PV) and its Controller Output (CO). In the absence of a bump test, tuning a plant’s PID controllers is little more than guesswork.

There are various types of bump tests that can be performed. The Step, Pulse, Doublet and PBRS are among the most commonly used. Some are more practical than others. Here we focus on the Pulse and Doublet tests since both allow practitioners to observe the process moving in opposite directions.

Pulse Test

The Pulse test involves the execution of two steps both in succession and in opposite directions. It begins by moving a controller’s Set Point (SP) in one direction. Best-practice is to move SP by a value that is 3-4 times the noise evident in the process. When the measured Process Variable (PV) shows a response to the change the SP is then stepped in the opposite direction and returned to its original value. While the Pulse test shows the process moving in both directions, it only reveals one-half of a process’ dynamic behavior. As such it is not the best test. The Doublet is the superior option.

Doublet Test

The Doublet test is essentially two Pulse tests that are conducted in rapid succession and that span both sides of a controller’s normal range of operation. Like the Pulse test the Doublet begins by moving the controller’s SP in one direction so that a clear response to the PV results. A key difference comes into play once the process initially responds to the change. Instead of returning the SP to its original value the SP is moved in the opposite direction and to the other side of the process’ operating range. Note that it’s not necessary for the process to settle at either of these two new SP values. The test is completed by returning the controller’s SP to its original value.

Why is the Doublet Test the best?

Whenever practical Control Station highly recommends the Doublet Test when tuning PID control loops. The Doublet provides data that is representative of a controller’s full range of operation. In contrast with a Pulse that only examines one side of a controller’s operating range, the model and tuning parameters resulting from a Doublet test allow for safer and more effective control.

These resources offer related content:

How Do I Calculate Gain? What Is the Difference Between Process Gain and Controller Gain?

Gain Is an Important Parameter So Important That There Are Two That You Need to Know Among practitioners who tune PID control loops manually most note their focus on calculating the Gain. What is sometimes overlooked is that there are two different Gain values – one for the...
Iconic-Mark_Inverted-Color

Overview of Cascade Control

While Cascade Control is generally considered an advanced control strategy, it is only marginally more complex to implement than Single Loop Control.  More often than not it is applied to improve the performance of a slow process such as temperature that demonstrates sluggish behavior.  Essentially...
Iconic-Mark_Inverted-Color

How to Model a PID Loop

As stated in a previous post, tuning PID controllers is a multi-step process. After you gather your data from your step test, the next step in the process is fitting a model to your Process Data. Fitting a model involves the analysis of bump test...

Still looking for more?

Now that you’ve gotten the basics, connect with our team to learn how our people, processes and technologies can help you optimize.